CONTROLLERS

The controller features a large display for data visualisation and is integrated in a housing designed for harsh field conditions. It enables precise process monitoring, pump control, flow measurement and limit value monitoring.

HART TO MODBUS INDICATOR

HMI, HART to MODBUS Indicator is designed to accept HART signals from field instruments in multi drop mode and convert standard variables into fixed MODBUS address registers. This is useful to accept / read exact values available for Flow, Pressure, Temperature transmitters in digital form in the control room eliminating errors in Analog input acquisition and process systems. User friendly messages to understand status of the instrument and actual values of HART slaves connected on the loop.The engineering units are acquired from the HART slaves hence reduced efforts for programming. User selectable baud rate for MODBUS Master on DIP switch. Isolated HART and RS485 port is available.



Technical Specification

Supply 230Volt AC
Input Hart
Output RS485
Communication Settings 8 way DIP switch for baud rates from 9600,19200,38400, 57600 & station ID from 1 to 64 for MODBUS side.
No of Slaves 15 HART slave units
MODBUS RTU On MODBUS RTU (Master) HMI gives Floating point value of Current, Primary, Secondary, Third & forth Variables. Engineering units for 4 variables & Device information like device ID, MFR'S code,hardware, software version etc. for HART slave units. (maximum 15). HART slave status indication in MODBUS registers